EXAIR NEMA 4 NHP Cabinet Cooler® Systems

A dust and oil tight, splash resistant EXAIR NEMA 4 Non Hazardous Purge Cabinet Cooler® System provides a slight positive pressure in the enclosure to keep contaminants from entering small holes or conduits. They are available with a thermostat control. Each of these systems will include a water-dirt filter separator to prevent water condensate and dirt from entering your enclosure and cold air distribution kit used to direct the air for circulation or on to hot spots. NEMA 4 (IP66) Cabinet Coolers are available in many cooling capacities for large and small control panels. All Cabinet Coolers are UL Listed and CE compliant. They are a low cost, reliable way to cool and purge electronic control panels. EXAIR Cabinet Coolers incorporate a vortex tube to produce cold air from compressed air - with no moving parts. The compact Cabinet Cooler can be installed in minutes through a standard electrical knockout.

Product BTU/Hr Solenoid Valve (Standard) Or ETC (Upgrade Voltage Material Type

High Temp Or NHP

Vortex Capacity

Air Inlet Filter
exair-nhp4604 275 N/A N/A Aluminum NEMA 4 Cabinet Cooler Only Non Hazardous Purge 4 SCFM (113 SLPM) 1/8 FNPT N/A
exair-nhp4608 550 N/A N/A Aluminum NEMA 4 Cabinet Cooler Only Non Hazardous Purge 8 SCFM (227 SLPM) 1/8 FNPT N/A
exair-nhp4615 1,000 N/A N/A Aluminum NEMA 4 Cabinet Cooler Only Non Hazardous Purge 15 SCFM (425 SLPM) 1/4 FNPT N/A
exair-nhp4625 1,700 N/A N/A Aluminum NEMA 4 Cabinet Cooler Only Non Hazardous Purge 25 SCFM (708 SLPM) 1/4 FNPT N/A
exair-nhp4630 2,000 N/A N/A Aluminum NEMA 4 Cabinet Cooler Only Non Hazardous Purge 30 SCFM (850 SLPM) 1/4 FNPT N/A
exair-nhp4640 2,800 N/A N/A Aluminum NEMA 4 Cabinet Cooler Only Non Hazardous Purge 40 SCFM (1,133 SLPM) 1/4 FNPT N/A

Performance:

NEMA 4 (IP66) Non Hazardous Purge Cabinet Cooler

Model Capacity Sound Level dBA
Btu/hr. Watts
NHP4604 275 80 59*
NHP4608 550 162 67*
NHP4615 1,000 293 73
NHP4625 1,700 498 80
NHP4630 2,000 586 80
NHP4640 2,800 821 82
*With optional cold muffler installed. Cooling Capacity at 100 PSIG (6.9 BAR) Supply Pressure.

Dimensions:

exair-dim4sm

 

exair-dim4lg

 

Models: 4604, 4608 

Models: 4615, 4625, 4630, 4640

Applications:

  • Programmable controllers
  • Line control cabinets
  • Motor control centers
  • Relay panels
  • NC/CNC systems
  • Modular control centers
  • CCTV cameras
  • Computer cabinets
  • Cool laser housings
  • Electronic scales

NEMA 4 Cabinet Cooler Advantages:

  • Low cost
  • Compact
  • Cooling capacities up to 5,600 Btu/hr. (1,641 Watts)
  • Quiet
  • Install in minutes
  • Maintain NEMA 4 integrity (IP66)
  • Stabilize enclosure temperature and humidity
  • No CFC's
  • No moving parts - maintenance free
  • Mount in standard electrical knockout
  • Stop nuisance tripping
  • Stop heat damage
  • Eliminate fans and filters
  • Eliminate lost production
  • Stop circuit drift
  • Stop dirt contamination
  • Provide washdown protection

Models:

NEMA 4 (IP66) Cabinet Cooler

Model Btu/hr. (Watts)
4604 275 (80)
4608 550 (162)
4615 1,000 (293)
4625 1,700 (498)
4630 2,000 (586)
4640 2,800 (821)

Accessories:

exair-sidemountfamEXAIR's Side Mount Kits make mounting on the side of an electrical enclosure possible when there is limited space on the top or side. (NEMA 4 and 4X Cabinet Cooler Systems must be mounted vertically.) Side Mount Kits maintain the NEMA rating of large and small NEMA Type 12, 4, and 4X enclosures. they mount in a standard electrical knockout (1-1/2 NPS). Side Mount Kits for NEMA 12 Cabinet Cooler Systems have an aluminum construction. Those for NEMA 4 and 4X Cabinet Cooler Systems are Type 303 or Type 316 stainless steel.

How It Works:

exair-cabinet-coolers-how-it-works

Compressed air enters the vortex tube powered Cabinet Cooler and is converted into two streams, one hot and one cold. Hot air from the vortex tube is muffled and exhausted through the vortex tube exhaust. The cold air is discharged into the control cabinet through the cold air distribution kit. The displaced hot air in the cabinet rises and exhausts to atmosphere through the cabinet air exhaust at a slight positive pressure. Thus, the control cabinet is both cooled and purged with cool, clean air. Outside air is never allowed to enter the control panel.

Cabinet Cooler Standards and Certifications

OSHA Safe!

EXAIR's Cabinet Cooler Systems comply with OSHA's Safety Requirements, the EU General Product Safety Directive (2001/95/EC) and meet the noise limitation requirements of the EU Machinery Directive (2006/42/EC). In addition, Cabinet Cooler Systems are Listed to applicable UL Standards and requirements by Underwriters' Laboratories. All sound level measurements are taken at 3 feet away.

Conflict Mineral Free

Look for this symbol to designate conflict mineral free products throughout our website. EXAIR supports Section 1502 of the Dodd-Frank Wall Street Reform and Consumer Protection Act and we are committed to compliance with the conflict minerals rule in order to curb the illicit trade of tin, tantalum, tungsten and gold in the DRC region. EXAIR is using the CMRT 3.02 template to document our supply chain and commitment to conflict free products.

Resources

EXAIR Cabinet Cooler - Small NEMA 4/4X Install Sheet

EXAIR Cabinet Cooler - Small NEMA 4/4X Install Sheet

Download
EXAIR Catalog

EXAIR Catalog

Download
EXAIR Cabinet Cooler Sizing Guide

EXAIR Cabinet Cooler Sizing Guide

Download
EXAIR White Paper: Cabinet Cooler System Advantages

EXAIR White Paper: Cabinet Cooler System Advantages

Download
EXAIR White Paper: Cabinet Coolers End Costly Shutdowns

EXAIR White Paper: Cabinet Coolers End Costly Shutdowns

Download
EXAIR White Paper: Total Cost of Ownership - Comparison of Popular Electronic Enclosure Coolers

EXAIR White Paper: Total Cost of Ownership - Comparison of Popular Electronic Enclosure Coolers

Download

Talk to one of our Experts

Reach out to our team of Spraying, Pumping, Filtering, Valve, and Systems Specialists today. We know we can help you with any municipal or industrial application challenges.